3412C (50 HZ) | 680-900 kVA Diesel Generator

Request Info

Contact Us For Price

SPECS SUMMARY

Maximum Rating900 kVA
Minimum Rating680 kVA
Emissions/Fuel StrategyLow Fuel Consumption
Voltage380 to 415 Volts
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Specifications

Maximum Rating900 kVA
Minimum Rating680 kVA
Emissions/Fuel StrategyLow Fuel Consumption
Voltage380 to 415 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Prime
Engine Model3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore5.4 in (137.2 mm)
Stroke6 in (152.4 mm)
Displacement1648.86 in³ (27.02 l)
Compression Ratio13:01
AspirationTA
Fuel SystemPump and Lines
Governor TypeADEM™ A5
Length - Maximum162.4 in (4125 mm)
Width - Minimum75 in (1906 mm)
Width - Maximum78.3 in (1989 mm)
Height - Maximum75 in (1906 mm)
Dry Weight - Genset (minimum)12039 lb (5461 kg)
Dry Weight - Genset (maximum)13030 lb (5910 kg)

Benefits and Features

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment

  • Air cleaner, single element canister type with service indicator
  • EMCP 4.2B
  • Customer data link (Modbus RTU)
  • 2 Programmable relay outputs (Form C)
  • Features include:
  • Voltage adjust
  • Failure to start (overcrank)
  • Volts (L-L & L-N)
  • Reverse power (kW) (32)
  • Accessory module data link
  • Over/under voltage (27 / 59)
  • Speed adjust
  • Low coolant temperature
  • Oil pressure (psi, kPa or bar)
  • Environmental sealed front face
  • Generator temperature monitoring module
  • DC volts
  • Serial annunciator module data link
  • Reverse reactive power (kVAr) (32RV)
  • Amps (per phase & average)
  • High coolant temperature
  • 24 Volt DC operation
  • Communications
  • Power factor (per phase & average)
  • Compatible with the following optional modules:
  • Low coolant level
  • Text alarm/event descriptions
  • Digital I/O module
  • 6 programmable digital inputs
  • Low oil pressure
  • Remote Serial annunciator
  • Engine cycle crank
  • Local annunciator
  • Digital indication for:
  • Over/under frequency (81 o/u)
  • Generator phase sequence
  • Emergency stop
  • kVAr (per phase, average & percent)
  • Run/auto/ stop/control
  • Operating hours
  • kVA (per phase, average & percent)
  • Warning/shutdown with common LED indication of shutdowns for:
  • Emergency stop pushbutton
  • Frequency (Hz)
  • coolant temperature
  • Overspeed
  • 4 programmable relay outputs (Form A)
  • kW-hr (total)
  • 2 Programmable digital outputs
  • Remote CAN annunciator
  • Overcurrent (50 / 51)
  • kW (per phase, average & percent)
  • RPM
  • Programmable protective relaying functions:
  • Radiator with guard (Sized for 50 degrees C)
  • Coolant level shutdown
  • Coolant drain line with valve, piped to edge of base
  • Fan and belt guards
  • Caterpillar extended life coolant
  • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
  • Primary and Secondary fuel filters
  • Fuel priming pump
  • Flexible fuel lines terminated on base
  • Water seperator
  • 2:1 Volts/Hz
  • Busbar termination
  • 3-phase sensing
  • Class H insulation
  • Reactive droop
  • VR6 voltage regulator
  • SR4B self excited
  • 12 Leads
  • Class F temperature rise
  • Cat electronic governor
  • Oil drain line with valve, piped to edge of base
  • Lubricating oil
  • Oil filter
  • Fumes disposal, piped to front of radiator
  • Base, formed steel with linear vibration isolators between base and engine-generator
  • 45 amp Charging alternator
  • Battery with rack, cables
  • Fuel shutoff solenoid
  • 24 volt starting motor

Optional Equipment

  • Heavy duty air cleaners
  • Dual element air cleaners
  • Open element air cleaners
  • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
  • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
  • Generator temperature monitoring package
  • EMCP 4.4
  • First local annunicators
  • Vandal proof panel door
  • Remote custom annunicator
  • EMCP 4.3
  • Local discrete I/O package
  • Common alarm/shutdown relay
  • Ground fault relay
  • Generator running VFC
  • Radiator duct flange
  • Jacket water heaters
  • Eurasian Conformity (EAC) mark
  • Through wall installation kit
  • Mufflers
  • Manifold and turbocharger guards
  • Elbow kit
  • Permanent magnet excitation (PMG)
  • Space heater
  • Digital voltage regulator
  • Oversize and premium generators
  • Manual sump pump
  • Fuel tank base (1200 ltr)
  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor
  • Oversize batteries
  • Battery chargers
  • Battery disconnect switch
  • Heavy duty starting system
  • Electronic load share