DE88 GC (60 HZ) C4.4 | 80 kW Diesel Generator
Contact Us For Price
SPECS SUMMARY
Maximum Rating | 80 ekW |
Minimum Rating | 80 ekW |
Emissions/Fuel Strategy | Non Regulated |
Voltage | 220 to 480 Volts |
Specifications
Maximum Rating | 80 ekW |
Minimum Rating | 80 ekW |
Emissions/Fuel Strategy | Non Regulated |
Voltage | 220 to 480 Volts |
Frequency | 60 Hz |
Speed | 1800 rpm |
Duty Cycle | Standby |
Engine Model | C4.4, In-line 4, 4-cycle diesel |
Bore | 4.1 in (105 mm) |
Stroke | 5 in (127 mm) |
Displacement | 268.5 in (4.4 l) |
Compression Ratio | 17.25:1 |
Aspiration | Turbocharged |
Fuel System | Inline |
Governor Type | Mechanical |
Length - Maximum | 89.6 in (2275 mm) |
Width - Maximum | 43.3 in (1099 mm) |
Height - Maximum | 57.7 in (1465 mm) |
Dry Weight - Genset (maximum) | 1245 lb (2745 kg) |
Benefits and Features
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
- CE Certification Available
- CIS Certification Available
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
- C4.4, Inline 4 Cylinder, 4 Stroke Diesel
- Mechanical Governor
- A Frame Standard Alternator
- Single Wall 8 Hour Tank
- GCCP 1.1
- Cat GC Enclosure
- Enclosure Silencer
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
- Australia, CIS, Gulf Certification
- Certificate of Conformance
- Space Heater
- Low Fuel Level Shutdown
- Single Wall Tank With Containment
- Dual Wall 8 Hour Tank
- Low Fuel Level Alarm
- High Fuel Level Alarm
- Volt Free Contacts for Genset Running
- Earth Fault
- Panel Mounted Audible Alarm
- USB to RS485 Communications Device
- Emergency Stop with Key
- Earth Leakage
- Battery Charger
- Volt Free Contacts for Common Alarm
- Coolant Heater
- Standby Pack (Smart Jacket Water Heater, Battery Charger)
- Battery
- Low Coolant Level Shutdown
- 3 Pole Circuit Breaker 160A
- 3 Pole Circuit Breaker 125A
- 3 Pole Circuit Breaker 200A
- 3 Pole Circuit Breaker 400A
- 4 Pole Circuit Breaker 160A
- 4 Pole Circuit Breaker 125A
- 3 Pole Circuit Breaker 250A
- 4 Pole Circuit Breaker 250A
- 4 Pole Circuit Breaker 200A
- Circuit Breaker Padlock
- 4 Pole Circuit Breaker 400A
- Neutral Earth Link
- Overload via Alarm Switch on Breaker
- PGS Test Report @ 1.0PF
- PGS Test Report @ 0.8PF