Request Info

Contact Us For Price

SPECS SUMMARY

Frequency60 Hz
Natural Gas Rating300 eKW
Emissions/Fuel StrategyU.S. EPA Certified for Non-Emergency Application
Engine Model14.2 L Spark - Ignited
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Specifications

Frequency60 Hz
Natural Gas Rating300 eKW
Emissions/Fuel StrategyU.S. EPA Certified for Non-Emergency Application
Engine Model14.2 L Spark - Ignited
Compression Ratio9.5:1
Displacement864.71 in³ (14.17 l)
Speed1800 rpm
Fuel SystemElectronic
Bore5.31 in (135 mm)
Stroke6.5 in (165 mm)
Length136 in (3455 mm)
Width57.6 in (1463 mm)
Height66.1 in (1678 mm)
Weight6274 lb (2852 kg)

Benefits and Features

  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water

  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries.

Standard Equipment

  • Closed coolant recovery system
  • 50/50 Ethylene glycol antifreeze
  • Factory-installed radiator
  • Standard ambient temperatures up to 50°C (122°F)
  • Radiator and cooling fan complete with protective guards
  • Single element air filter
  • Low fuel pressure switch
  • Primary and secondary fuel shut-off
  • Fuel pressure test po
  • Dual lock off valves
  • Natural Gas or LP Vapor
  • NPT connection
  • Exhaust outlet with 3” pipe
  • Full load capacity alternator
  • Class H insulation material
  • Permanent magnet excitation
  • Matched to the performance and output characteristics of Cat engines
  • Class H insulation material
  • Integrated Voltage Regulator
  • Permanent magnet excitation
  • IP23 Protection
  • Full load capacity alternator
  • EMCP 4.2 Series generator set controller
  • Vibration isolaton (puck type)
  • Rubber vibration isolators
  • Engine electrical system
  • Battery cables
  • Solenoid activated starter motor
  • Solenoid activated starter motor
  • Electronic governor (non adjustable)
  • EMCP 4.2 Series generator set controller
  • Batteries with rack and cables
  • 12 volt starting motor

Optional Equipment

  • Charging alternator
  • Battery charger – UL Listed 10 amp
  • Jacket water heater
  • Battery heater
  • Suitable for Use as Service Equipment (SUSE)
  • UL 2200 package
  • Automatic transfer switches (ATS)
  • Enclosures: sound attenuated, weather protective
  • CSA Certification
  • Anti-condensation heater
  • Shunt trip and auxiliary contact breaker
  • Thermal magnetic or electronic trip MCCBs
  • Oversize and premium generators
  • Excitation: [ ] Permanent Magnet Excited (PM)
  • Anti-condensation heater