CN3586 Electric Motor for Gas Compression

Request Info

Contact Us For Price

SPECS SUMMARY

Type of EX-ProtectionClass 1 Division 2 Group A,B,C,D T3 (NEC or CEC)
Locked Rotor Amps540% Code E
InsulationClass F
No Load Current137 Amps
Get power built for your most demanding gas compression applications. Every Cat® electric motor is tested at each stage of production to make sure it performs reliably under load and according to your process requirements. High operating efficiency and low operating costs come with low noise levels and no emissions. Cat electric motors for gas compression are backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty.

Specifications

Type of EX-ProtectionClass 1 Division 2 Group A,B,C,D T3 (NEC or CEC)
Locked Rotor Amps540% Code E
InsulationClass F
No Load Current137 Amps
Service Factor1.15 SF (1.0 VFD)
Locked Rotor Torque60%
Enclosure Type/Method of CoolingWP-II
DutyContinuous
StandardsNEMA MG1
Connection of Stator WindingStar
Maximum Altitude - Before Derate3300 ft (1000 m)
Mounting DesignationF1 or F2
Rated Torque20555 lb/ft (27869 N·m)
Shaft8.5 in (216 mm)
Full Load Current458 Amps
Maximum Ambient Temperature104 °F (40 °C)
Number of Poles8
Electric Motor TypeSquirrel Cage Induction Motor
Full Load Speed894 rpm
Voltage/Frequency4000V & 4160V ± 10%/60 Hz
Temperature RiseClass B at rated load

Standard Equipment

  • Bearing RTDs for temperature monitoring
  • Insulated non-drive end bearings to reduce bearing currents
  • Anti-friction on 1500 hp (optional)
  • Designed for minimal vibration
  • Dynamic balancing at full operational speed
  • Fabricated copper squirrel cages
  • Forged, keyless shaft
  • AISI 4140/DIN42CrMo4 shaft
  • Radial air ducts ensure uniform and efficient cooling
  • Vacuum pressure impregnated with specially formulated epoxy resin
  • 2X RTDS per Phase
  • Space heater
  • Welded and machined stator core retains its rigidity throughout motor life to ensure a sealed and homogeneous insulation system that results in high dielectric strength, excellent heat transfer and the elimination of hazardous internal partial discharges